Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual
Page 174

174
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Appendix C
Specifications
1734‐IB8S Series B temperature versus aggregate current
per module ‐ derating for both horizontal and vertical
installations
Pulse width
525
μs
Pulse period
144 ms
Maximum field capacitance limit permitted per test
output
100 nF
Current, max (when used to control muting lamp)
25 mA (to avoid fault when used as a muted lamp output)
Current, min (when used to control muting lamp)
5 mA (at which fault indication is generated when used as
a muted lamp output)
Residual voltage, max
0.3 V
Output leakage current, max
0.1 mA
Short circuit protection
Yes
POINTBus
POINTBus current, max
110 mA
Power dissipation, max
(1)
3.0 W
Thermal dissipation, max
10.25 BTU/hr
Power dissipation, typical
(2)
2.25 W
Isolation Voltage
50 V (continuous), Basic Insulation Type between field
side and system.
No isolation between individual channels.
Type tested at 500V AC for 60 s.
Power bus, operating supply voltage
24V DC nom, Class 2
Power bus, operating voltage range
19.2…28.8V DC, Class 2
Power bus current (no load), max
25 mA
Attribute
1734-IB8S Series B
2.8 A
-20 °C
(-4 °F)
40 °C
(104 °F)
55 °C
(131 °F)
0.55 A