Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual
Page 189
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
189
Configuration Parameters
Appendix E
x
Input Point Operation Type
Single channel
Use as single channel.
Single
Dual channel
Use as a dual channel equivalent. This setting should be used only with
SmartGuard controllers.
Filter
1 Hz
Input filter
1 Hz
5 Hz
10 Hz
50 Hz
x
Safety Input Error Latch Time
0…65,530 ms
(in 10 ms increments)
Safety input errors are latched for this time so that they can be read by the
controller and are not missed if they clear themselves too quickly. One value for all
channels.
1000
Low Engineering
-30000…30000
Scaling value for inputs
0
High Engineering
-30000…30000
Scaling value for inputs
10,000
(2)
x
Tachometer Dual Low
Diagnostic
ON/OFF
Diagnostic that indicates if both channels are low.
Channels 0 and 1 share the same value and channels 2 and 3 share the same value.
Off
Tachometer Trigger
Falling edge (NPN)
Non-inverted input signal.
Falling edge
Rising edge (PNP)
Inverted input signal.
Tachometer Off Level
0…23V
(in 1 V increments)
Off-level for the Tachometer mode input signal.
5V
Tachometer On Level
1…24V
(in 1 V increments)
On-level for the Tachometer mode input signal.
11V
Sensor Power Mode
External
Sensors are getting their power from a separate power supply.
Module
x
Module
Sensors are getting their power from the module (recommended).
Alarm Enable
Disable
Enable or disable alarms.
We recommend disabling this feature when using the module in a GuardLogix
system (evaluate alarms using the application program). Enable this feature when
using the module in a SmartGuard system.
Disable
Enable
High High Alarm Level
-32768…32767
High High alarm trip point.
32767
Low Low Alarm Level
-32768…32767
Low Low alarm trip point.
-32767
High High - Low Low
Deadband
0…32767
Deadband on the High High and Low Low alarms.
0
High Alarm
-32768…32767
High alarm trip point.
332767
Low Alarm
-32768…32767
Low alarm trip point.
0
High - Low Deadband
0…32767
Deadband on the High and Low alarms.
0
x
Discrepancy Time
0…65,530
(in 10 ms increments)
Time period during which the channel values may be discrepant before an error is
reported.
100 ms
x
Discrepancy Deadband
0…32767
Tolerance range between channels in dual-channel mode (in engineering units)
0
x
Channel Offset
-32768…32767
Offset value for dual channel mode only (in engineering units).
0
(1) Parameters directly related to safety are marked with an x in the left column.
(2) 1000 for Tachometer mode.
Table 20 - Safety Analog Input Parameters (continued)
Parameter Name
(1)
Value
Description
Default