Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual
Page 70

70
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Chapter 4
Install the Module
Figure 39 - 4-wire Voltage or Tachometer Sensor (SIL 3)
Figure 40 - 4-wire Current Sensor (SIL 3)
Guidelines for Wiring Safety Analog Inputs on page 65
FE
FE
V0
V1
V2
V3
I0
I1
I2
I3
COM
COM
COM
COM
COM
COM
COM
COM
S0
S1
S2
S3
S0
S1
S2
S3
This wiring configuration may also be used for SIL 2 redundant Tachometer mode.
Signal Return and Common are at the same potential.
Field sensors are monitoring the same signal in a redundant configuration.
You must configure a safety discrepancy deadband between the two signals to achieve SIL 3.
SIL 2
4-wire
Sensor
1734-TOP3 Terminal Bases
Signal (V)
+24V
Cable Shield
Signal Return
Common
SIL 2
4-wire
Sensor
Signal (V)
+24V
Signal Return
Common
Cable Shield
See
and
for tachometer wiring detail.
FE
FE
V0
V1
V2
V3
I0
I1
I2
I3
COM
COM
COM
COM
COM
COM
COM
COM
S0
S1
S2
S3
S0
S1
S2
S3
Signal Return and Common are at the same potential.
Field sensors are monitoring the same signal in a redundant configuration.
You must configure a safety discrepancy deadband between the two signals to achieve SIL 3.
SIL 2
4-wire
Sensor
1734-TOP3 Terminal Bases
Signal (I)
+24V
Cable Shield
Signal Return
Common
SIL 2
4-wire
Sensor
Signal (I)
+24V
Signal Return
Common
Cable Shield