Technical specifications for series b modules, Safety digital input module specifications, Technical – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual
Page 173: Specifications for series b modules, For s
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
173
Specifications
Appendix C
Technical Specifications for
Series B Modules
Safety Digital Input Module Specifications
Attribute
1734-IB8S Series B
Safety Input
Inputs per module
8
Input type
Current sinking
Voltage, on-state input
11…30V DC, 3.5 mA @ 40 °C (104 °F), Class 2
11…28.8V DC, 3.5 mA @ 55 °C (131 °F), Class 2
1734‐IB8S Series B temperature versus safety input
voltage (max) ‐ derating for both horizontal and vertical
installations
Voltage, off-state input, max
5V DC
Current, on-state input, min
3.3 mA
Current, off-state, max
1.3 mA
IEC 61131-2 (input type)
Type 3
Reaction time
<16.2 ms
Pulse Test Output
Output type
Current sourcing
Number of sources (T0, T1M, T2, T3M)
4
Test output current (each output point)
0.7 A @ 40 °C (104 °F)
0.5 A @ 55 °C (131 °F)
1734‐IB8S Series B temperature versus current per test
output point ‐ derating for both horizontal and vertical
installations
Aggregate current of test outputs per module
2.8 A @ 40 °C (104 °F)
0.55 A @ 55 °C (131 °F)
30V
-20 °C
(-4 °F)
40 °C
(104 °F)
55 °C
(131 °F)
28.8V
0.7 A
-20 °C
(-4 °F)
40 °C
(104 °F)
55 °C
(131 °F)
0.5 A