F - i/o assemblies, Input assemblies, Appendix f – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual
Page 191: I/o assemblies, Appendix

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
191
Appendix
F
I/O Assemblies
Input Assemblies
Topic
Page
Using Data from Modules Configured via the Generic Profile
Table 21 - 1734-IB8S Input Assemblies
Instance
Decimal
(hex)
Connection
Type
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
516 (204h)
Safety and
Standard
0
Safety Input
7
Safety Input
6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
548 (224h)
Safety Only
0
Safety Input
7
Safety Input
6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 7
Safety Input
6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
768 (300h)
Standard Only
0
Reserved
Input Power
Error
788 (314h)
Safety and
Standard
0
Safety Input
7
Safety Input
6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Combined
Safety Input
Reserved
Input Power
Error
(1)
Reserved
Reserved
Reserved
Muting Lamp 3 Muting Lamp 1
820 (334h)
Safety and
Standard
0
Safety Input
7
Safety Input
6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input
7
Safety Input
6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
2
Reserved
Input Power
Error
Reserved
Muting Lamp 3 Muting Lamp 1
868 (364h)
Safety and
Standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input
7
Safety Input
6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
2
Reserved
Test Output 3
Test Output 2
Test Output 1
Test Output 0
3
Reserved
Input Power
Error
Reserved
Muting Lamp 3 Muting Lamp 1
899 (383h)
Standard
0
Reserved
Input Power
Error
1
Reserved
Test Output 3
Test Output 2
Test Output 1
Test Output 0
(1) This data is diagnostic only and does not have safety integrity.