Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual
Page 148

148
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Chapter 8
Replacing POINT Guard I/O Modules
6. Verify that the (NS) Network Status indicator is flashing on the correct
module and click OK to set the SNN on that device.
RSNetWorx for DeviceNet software confirms that the SNN has ben set.
Once the download successfully completes, the main project view displays
this message: ‘The device at address
xx has been downloaded. Any device-
specific messages related to the download operation are displayed
separately.’
Assuming this is the proper configuration from the original DNT file, the
SNN and configuration signature now match that of the original. If you
are already connected to the controller, a connection is made. The
controller does not need to be taken out of Run mode to download to the
replacement module.