Replacement with ‘configure always’ enabled, Replacement with ‘configure – Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual
Page 145

Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
145
Replacing POINT Guard I/O Modules
Chapter 8
3. Click the Safety tab.
4. Click Reset Ownership.
5. Click OK.
6. Follow your company-prescribed procedures to functionally test the
replaced I/O module and system and to authorize the system for use.
Replacement with ‘Configure Always’ Enabled
When the ‘Configure Always’ feature is enabled, the controller automatically
checks for and connects to a replacement module that meets all of the following
requirements:
• The controller has configuration data for a compatible module at that
network address.
• The module is in out-of-box condition or has an SNN that matches the
configuration.
If the project is configured for ‘Configure Always’, follow the appropriate steps to
replace a POINT Guard I/O module.
ATTENTION: Enable the ‘Configure Always’ feature only if the entire CIP Safety
Control System is not being relied on to maintain SIL 3 behavior during the
replacement and functional testing of a module.
Do not place modules that are in the out-of-box condition on a CIP Safety network
when the Configure Always feature is enabled, except while following this
replacement procedure.