Chapter 8
Replacing POINT Guard I/O Modules
controller to download the proper module configuration, and re-establish the
safety connection.
Scenario 1 - Replacement Module Is Out-of-box and Safety Signature Exists
1. Remove the old I/O module and install the new module.
2. Right-click the replacement POINT Guard I/O module and choose
Properties.
3. Click
to the right of the safety network number to open the Safety
Network Number dialog box.
4. Click Set.
Table 11 - Replacing a Module
GuardLogix Safety
Signature Exists
Replacement
Module Condition
Action Required
No
No SNN
(Out-of-box)
None. The module is ready for use.
Yes or No
Same SNN as original
safety task
configuration
None. The module is ready for use.
Yes
No SNN
(Out-of-box)
See
Scenario 1 - Replacement Module Is Out-of-box and Safety
.
Yes
Different SNN from
original safety task
configuration
See
Scenario 2 - Replacement Module SNN Is Different from Original
and Safety Signature Exists on page 143.
No
Scenario 3 - Replacement Module SNN Is Different from Original
and No Safety Signature Exists on page 144
.