Configure the Module for a SmartGuard Controller
Chapter 6
5. Double-click each Engineering Units Alarms group to display parameters
for editing.
Parameter Name
Value
Description
Default
High High/Low Low Alarm
Enable
Disable
Enable or disable alarms.
Disable
Enable
High High Alarm
-32768…32767
Follow these guidelines when setting the alarm values.
• The High High alarm value must be greater than or equal to the High alarm value.
• The High alarm value must be greater that the Low alarm value.
• The Low Low alarm value must be less than or equal to the Low alarm value.
• These values are based on the Engineering units
32767
Low Low Alarm
-32768…32767
0
High Alarm
-32768…32767
32767
Low Alarm
-32768…32767
0
High High/Low Low Alarm
Deadband
0…32767
Deadband on the High High and Low Low alarms.
0
High/Low Alarm Deadband
0…32767
Deadband on the High and Low alarms.
0