Rockwell Automation 1734-IE4S POINT Guard I/O Safety Modules User Manual User Manual
Page 25
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
25
Safety Inputs, Safety Outputs, and Safety Data
Chapter 2
Figure 5 - Test Pulse in a Cycle
For the 1734-IB8S module, the pulse width (X) is typically 525 μs; the pulse
period (Y) is typically 144 ms.
When the external input contact is closed, a test pulse is output from the test
output terminal to diagnose the field wiring and input circuitry. By using this
function, short-circuits between inputs and 24V power, and between input signal
lines and open circuits can be detected.
Figure 6 - Short-circuit between Input Signal Lines
X
OUT
Y
On
Off
IN+
24V
24V
0V
COM
T0
T1
IN0
IN1
External Contact
Short-circuit between Input Signal Lines and Power
Supply (positive side)
External Contact
Short-circuit between Input Signal Lines
44079