PLC Ladder Logic Programming
The 1305 or 1336 PLUS drive in this example sends the following
Logic Status Data to the PLC.
This example program for the 1305 or 1336 PLUS drive provides
basic control functions, including starting, stopping, clearing faults,
displaying drive status, controlling drive frequency reference, and
displaying drive frequency feedback. Two words of control I/O have
been enabled for this program by accepting the module’s default
configuration and by entering 2 for the Input Size and Output Size in
RSNetWorx.
Logic Status Bits
Function
Description
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
X Enabled
1=Enabled, 0=Not Enabled
X
Running
1=Running, 0=Not Running
X
Command Direction 1=Forward, 0=Reverse
X
Rotating Direction
1=Forward, 0=Reverse
X
Acceleration
1=Accelerating, 0=Not
X
Deceleration
1=Decelerating, 0=Not
X
Warning
1=Warning Present, 0=Not
X
Fault
1=Faulted, 0=Not Faulted
X
At Reference
1=At Speed, 0=Not At Speed
X
X
X
Local
000=Terminal I/O has Local
001=Port 1 has Local
010=Port 2 has Local
011=Port 3 has Local
100=Port 4 has Local
101=Port 5 has Local
110=Port 6 has Local
111=Multiplexed Control
X
X
X
X
Reference Source
0000=External Reference 1
0001 – 0111=Presets 1 – 7
1000=External Reference 2
1001 – 1110=Port 1 – 6 Direction
1111=Jog