Installation
SCANport Cables
When selecting the SCANport cable to connect the module to the
SCANport product, you need to:
•
Use an Allen-Bradley SCANport cable. Refer to the table below.
•
Do not exceed 10 meters (33 feet) of cable between the
SCANport product and module.
•
Keep SCANport cables away from high power cables to guard
against introducing noise into your system.
ControlNet Cable Taps
A tap connects a node on the ControlNet network, such as a module,
to the cable system via an integral 1 m (39.6 in.) drop cable. When
selecting a tap to connect the module to the ControlNet network, you
need to:
•
Determine if your network uses a redundant media system. If so,
you will need two taps.
•
Use one or two Allen-Bradley tap(s). Refer to the table below.
For more information on ControlNet taps and ControlNet networks,
refer to Publication 1786-6.2.1, ControlNet Cable System Planning
and Installation Manual.
Male to Male Connection
➀
Male to Female Connection
Length
Catalog Number
Length
Catalog Number
1/3 m
1202-C03
1/3 m
1202-H03
1 m
1202-C10
1 m
1202-H10
3 m
1202-C30
3 m
1202-H30
9 m
1202-C90
9 m
1202-H90
➀
For most installations, a male-to-male connection on the cable is required.
Type
Catalog Number
Straight T-Tap
1786-TPS
Straight Y-Tap
1786-TPYS
Right-Angle T-Tap
1786-TPR
Right-Angle Y-Tap
1786-TPYR