Rockwell Automation 20Y PowerFlex Active Front End User Manual
Page 99
Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
99
Programming and Parameters
Chapter 4
DY
NAMIC C
O
NTROL
Curr
en
t L
oo
p
064
[Active I Ref]
Displays the active current reference.
Default:
Min/Max:
Units:
Read Only
+/- 3200.0 Amp
0.1 Amp
065
[Reactive I Ref]
If selected by [Reactive I Sel], this parameter sets the reference for the reactive current. This can be
used for power factor correction of the power system. Positive value gives inductive current; negative
value gives capacitive current. The maximum reactive current is limited by the following formula:
Default:
Min/Max:
Units:
0.0 Amp
+/- Based on parameter 032 [Rated Amps]
0.1 Amp
066
[Active I Kp]
Sets the active current controller gain.
Default:
Min/Max:
Units:
400
0/4000
None
067
[Active I Ki]
Sets the integral gain of the active current controller.
Default:
Min/Max:
Units:
0.0266 sec
0.0000/6.0000 sec
0.0001 sec
068
[Reactive I Kp]
Sets the synchronization controller gain.
Default:
Min/Max:
Units:
2000
0/32000
None
069
[Reactive I Ki]
Sets the integral of the synchronization controller.
Default:
Min/Max:
Units:
0.040 sec
0.000/20.000 sec
0.001 sec
070
[Reactive I Sel]
Selects the source from which the reactive current is taken.
Default:
Options:
0
0
1
2
React I Ref
React I Ref
Analog In1
Analog In2
Limits
075
[Motor Power Lmt]
Sets the limit for motoring power on the AC line.
Default:
Min/Max:
Units:
300.0%
0.1/300.0%
0.1%
076
[Regen Power Lmt]
Sets the limit for regenerative power allowed to the AC line.
Default:
Min/Max:
Units:
-300.0%
-0.1/-300.0%
0.1%
077
[Current Lmt Val]
Sets the current limit value.
Default:
Min/Max:
Units:
1.5 x [Rated Amps]
0.0/Based on Unit Rating
0.1 Amps
078
[DC Bus Lo Alarm]
Sets the lowest acceptable DC bus voltage for the application. A warning is indicated if the DC bus
voltage falls below the value of this parameter.
Default:
Min/Max:
Units:
Based on Unit Rating
0.0/2000.0V DC
0.1V DC
079
[DC Bus Hi Alarm]
Sets the highest acceptable DC bus voltage for the application. A warning is indicated if the DC bus
voltage exceeds the value of this parameter.
Default:
Min/Max:
Units:
Based on Unit Rating
0.0/2000.0V DC
0.1V DC
080
[DC Ref Lo Lmt]
Displays the limit value of the DC bus reference low limitation, which is calculated based on the
voltage class x 1.35 x 1.05.
Default:
Min/Max:
Units:
Read Only
0.0/1500.0V DC
0.1V DC
081
[DC Ref Hi Lmt]
Displays the limit value of the DC bus reference high limitation, which is calculated based on the
voltage class x 1.35 x 1.3 (for 400/480V units) or voltage class x 1.35 x 1.15 (for 600/690V units).
Default:
Min/Max:
Units:
Read Only
0.0/1500.0V DC
0.1V DC
082
[Ground I Lvl]
Sets the limit value of ground current in % of the unit rating before a ground current alarm or fault is
activated. For AFE parallel operation, the values in all AFEs must be set to 100%.
Default:
Min/Max:
Units:
50.0%
0.0/100.0%
0.1% (Based on unit rating)
Fil
e
Gr
oup
No.
Parameter Name & Description
Values
Maximum Reactive I Ref = P032 [Rated Amps]
2
- P004 [Active Current]
2