Figure 15 – Rockwell Automation 20Y PowerFlex Active Front End User Manual
Page 36
36
Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
Chapter 1
AFE in IP20 2500 MCC Style Enclosure—Installation/Wiring
Figure 15 - AFE Frame 13 Power Terminal Locations in IP20 2500 MCC Style Enclosure
Table 3 - AFE Frame 13 Power Terminal Specifications in IP20 2500 MCC Style Enclosure
(Shown with
enclosure doors
and side removed)
FRONT VIEW
RIGHT SIDE VIEW
Item
Name
Frame
Description
Wire Size Range
(1)
(2)
Torque
Terminal Bolt
Size
(3)
(4)
Maximum
Minimum
Recommended
➊
Input Power Terminals
L1, L2, L3
13
Input power
380 mm
2
(750 MCM)
53 mm
2
(1/O AWG)
50 N•m
(442 lb•in)
N/A
➋
SHLD Terminal, line PE,
Ground
13
Terminating point for wiring shields
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N•m
(354 lb•in)
M5-M10
➌
SHLD Terminal, motor
PE, Ground
➍
DC Bus
13
DC output (using cable)
380 mm
2
(750 MCM)
2.1 mm
2
(14 AWG)
70 N•m
(620 lb•in)
M12
DC output (using Right Side Splice Kit
SK-Y1-BUSSPLICE-F13R)
—
—
40 N•m
(354 lb•in)
M10
DC output (using Left Side Splice Kit
SK-Y1-BUSSPLICE-F13L)
—
—
(1) Maximum/minimum sizes that the terminals will accept - these are not recommendations.
(2) Do not exceed maximum wire size. Parallel connections may be required.
(3) These connections are bus bar type terminations and require the use of lug type connectors.
(4) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt to avoid damage to the terminal.