beautypg.com

Manually clearing faults, Fault and alarm descriptions – Rockwell Automation 20Y PowerFlex Active Front End User Manual

Page 117

background image

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

117

Troubleshooting

Chapter 5

Manually Clearing Faults

Fault and Alarm Descriptions

Steps

1. Press the HIM

(Escape) key to acknowledge the fault.

The fault information is removed so that you can use the HIM.

2. Address the condition that caused the fault.

The cause must be corrected before the fault can be cleared.

3. After corrective action has been taken, clear the fault with one of these methods:

Press the HIM

(Stop) key.

Cycle power to the AFE.
Set AFE parameter 121 - [Fault Clear] to ‘1’ (Clear Faults).
‘Clear Faults’ by using the HIM Diagnostic menu.

Esc

Table 21 - Fault/Alarm Types, Descriptions, and Actions

No.

Name

Fa

ul

t

Al

arm

Description

Action (if appropriate)

1

PrechargeActv

The charging switch is open, when the START
command has been given.
Faulty operation
Component failure

Reset the fault and restart.
Should the fault re-occur, contact Technical
Support (see

page 124

).

2

Auxiliary In

The auxiliary input interlock is open.

Check all remote wiring.

4

DC UnderVolt


The DC bus voltage fell below the minimum value of
333V for 400/480V AFEs or 461V for 600/690V AFEs.
You can enable/disable this fault with parameter 120
[Fault Config].

Monitor the incoming AC line for low voltage or
power interruption.

5

DC OverVolt

The DC bus voltage exceeded the maximum value of
911V for 400/480V AFEs or 1200V for 600/690V AFEs.

1. Check if the AFE was in a regenerative current

limit condition, which may indicate an excess
regenerative load.

2. Adjust parameter [Regen Power Lmt].

3. Monitor incoming AC line for high voltage or

voltage transients.

7

Overload

When input current exceeds 125% for 60 seconds or
150% for 30 seconds. The overload is a linear type in
counting up.

Reduce the current consumption of the AFE or
increase parameter 133 [Cnvrtr OL Factor].

8

HeatsinkOvrTp

➁ ➊

The heatsink temperature has exceeded the
maximum allowable value.
85 °C = Alarm
90 °C = Fault

1. Verify that the maximum ambient

temperature has not been exceeded.

2. Check the fans (including the ASIC board on

frame 10 and higher converters).

3. Check for an excess load.

9

IGBT OverTemp

The output transistors have exceeded their maximum
operating temperature due to an excessive load.

1. Verify that the maximum ambient

temperature has not been exceeded.

2. Check the fan or fans.

3. Check for an excess load.

10

System Fault

A hardware problem exists in the power structure.

1. Cycle the power.

2. Verify the fiber optic connections.

3. Contact Technical Support (see

page 124

).

4. If the problem persists, replace the converter

unit.

12

AC OverCurr

The AC line current has exceeded the hardware
current limit.

Check programming for an excess load or other
causes of excess current.