AFE in IP21 Rittal Enclosure—Installation/Wiring
Chapter 2
Power Terminals for AFE in IP21 Rittal Enclosure
The following figures and tables show the power terminal locations and
specifications for AFE Frames 10 and 13 in an IP21 Rittal enclosure.
Figure 30 - AFE Frame 10 Power Terminal Locations in IP21 Rittal Enclosure
Table 12 - AFE Frame 10 Power Terminal Specifications in IP21 Rittal Enclosure
(Shown with
enclosure doors
removed)
FRONT VIEW
RIGHT SIDE VIEW
Item
Name
Frame
Description
Wire Size Range
(1)
(2)
Torque
Terminal Bolt
Size
(3)
(4)
Maximum
Minimum
Recommended
➊
Input Power Terminals
L1, L2, L3
10
Input power
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N•m
(354 lb•in)
M10
➋
SHLD Terminal, PE,
Ground
10
Terminating point for wiring shields
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
40 N•m
(354 lb•in)
M10
➌
(DC–, DC+)
10
DC output
300 mm
2
(600 MCM)
2.1 mm
2
(14 AWG)
70 N•m
(620 lb•in)
M12
(1) Maximum/minimum sizes that the terminals will accept - these are not recommendations.
(2) Do not exceed maximum wire size. Parallel connections may be required.
(3) These connections are bus bar type terminations and require the use of lug type connectors.
(4) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt to avoid damage to the terminal.