Rockwell Automation 20Y PowerFlex Active Front End User Manual
Page 96

96
Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
Chapter 4
Programming and Parameters
MON
IT
O
R
Meterin
g
018
[Cmd DC Volt]
Displays the commanded DC bus voltage reference.
Default:
Min/Max:
Units:
Read Only
0.0/1500.0V DC
0.1V DC
019
[Motoring MWh]
Displays the accumulated motoring MWh. This parameter may be reset with parameter 092 [Reset
Meters].
Default:
Min/Max:
Units:
Read Only
0.0/429496729.5 MWh
0.1 MWh
020
[Regen MWh]
Displays the accumulated regenerative MWh fed back to the AC line. This parameter may be reset with
parameter 092 [Reset Meters].
Default:
Min/Max:
Units:
Read Only
0.0/429496729.5 MWh
0.1 MWh
021
[Elapsed Run Time]
Displays the accumulated amount of time that the AFE has been in Run. This parameter may be reset with
parameter 092 [Reset Meters].
Default:
Min/Max:
Units:
Read Only
0.0/214748364.0 Hr
0.1 Hr
022
023
[Analog In1 Value]
[Analog In2 Value]
Displays the value of the signal at the analog inputs.
Default:
Min/Max:
Units:
Read Only
0.000/20.000 mA or -/+10.000V
0.001 mA or 0.001V
Con
ver
te
r Da
ta
030
[Rated kW]
Displays the nominal power rating of the AFE.
Default:
Min/Max:
Units:
Read Only
0.00/3000.00 kW
0.01 kW
031
[Rated Volts]
Displays the nominal input voltage class (400V, 480V, 600V, or 690V) of the AFE.
Default:
Min/Max:
Units:
Read Only
0.0/1000.0V AC
0.1V AC
032
[Rated Amps]
Displays the nominal AC input current rating of the AFE.
Default:
Min/Max:
Units:
Read Only
0.0/6553.5 Amps
0.1 Amps
033
[Control SW Ver]
Displays the Main Control Board software version of the AFE.
Default:
Min/Max:
Units:
Read Only
0.000/255.255
0.001