Rockwell Automation 20Y PowerFlex Active Front End User Manual
Page 110
110
Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
Chapter 4
Programming and Parameters
INPU
TS & OUTPUT
S
An
al
og O
utput
s
208
[Anlg Out Absolute]
Selects whether the signed value or absolute value of a parameter is used before being scaled to drive the analog
output.
209
[Analog Out1 Sel]
Selects the source for Analog Output 1.
Default:
Options:
0 = Input Volt
See Table
210
[Analog Out1 Hi]
Sets the Analog Output 1 value when the source value is at maximum.
Default:
Min/Max:
Units:
20.000 mA, 10.000V
4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V
211
[Analog Out1 Lo]
Sets the Analog Output 1 value when the source value is at minimum.
Default:
Min/Max:
Units:
0.000 mA, 0.000V
4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V
212
[Analog Out2 Sel]
Selects the source for Analog Output 2.
Default:
Options:
0 = AC Line Freq
See
Table
213
[Analog Out2 Hi]
Sets the Analog Output 2 value when the source value is at maximum.
Default:
Min/Max:
Units:
20.000 mA, 10.000V
4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V
214
[Analog Out2 Lo]
Sets the Analog Output 2 value when the source value is at minimum.
Default:
Min/Max:
Units:
0.000 mA, 0.000V
4.000/20.000 mA
-/+10.000V
0.001 mA
0.001V
Fil
e
Gr
oup
No.
Parameter Name & Description
Values
Bit
Definition
An
al
og
O
ut
2
An
al
og
O
ut
1
Default
x
x
x
x
x
x
x
x
x
x
x
x
x
x
1
1
Bit
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
1 = Absolute
0 = Signed
x = Reserved
Options
[Analog Out1 Lo] Value
[Analog Out1 Hi]
Value
Parameter [Anlg Out Absolut] =
Signed
Absolute
0
Input Volt
0V AC
0V AC
200% Rated
(2)
(2)
100% corresponds to parameter 031 [Rated Volts].
1
AC Line Freq
–63.0 Hz
0 Hz
63.0 Hz
2
Total Curr
0 Amps
0 Amps
200% Rated
(3)
(3)
100% corresponds to parameter 032 [Rated Amps].
3
Active Curr
–200% Rated
0 Amps
200% Rated
4
ReactiveCurr
–200% Rated
0 Amps
200% Rated
5
Input Curr R
0 Amps
0 Amps
200% Rated
6
Input Curr S
0 Amps
0 Amps
200% Rated
7
Input Curr T
0 Amps
0 Amps
200% Rated
8
DC Bus Volt
0V DC
0V DC
300% Rated
9
DC Bus Curr
–200% Rated
0 Amps
200% Rated
10
AC Line kW
–200% Rated
0 kW
200% Rated
(4)
(4)
100% corresponds to parameter 030 [Rated kW].
11
AC Line kVar
–200% Rated
0 kVar
200% Rated
12
AC Line kVA
0 kVA
0 kVA
200% Rated
13
Power Factor
-1.00
0
1.00
14
DC Bus V Ref
P080 [V DC]
P080 [V DC]
P081 [V DC]
15
Param Cntl
(1)
(1)
Parameter controlled analog output allows PLC to control analog outputs through datalinks.
Set in parameter 217 [Anlg Out1 Setpt] and parameter 218 [Anlg Out2 Setpt].
—
—
—
16
TestPt Data1
-32767
0
32767