Chapter 5

Troubleshooting

125

LCL OverTemp

The LCL Filter has been overheated or the signal is not
connected to input.

Check the LCL Filter sensor connections, the fan,
and fan power supply.

There are nine total thermal switches connected in series

to monitor temperature inside the coil of each filter inductor.

X52 is located on the LCL Filter.

128

Contact Fdbk

The input of the acknowledge signal from the main
contactor is missing.

Check if the main contactor is closed.
Check the wiring of the feedback signal.

133

DigInConflict

Digital input functions are in conflict.

Check the parameter settings to correct the
problem.

138

DCRefLowLim

DC voltage reference is less than the limit in
parameter 080 [DC Ref Lo Lmt].

Check the parameter setting.

139

DCRefHighLim

DC voltage reference exceeds the limit in parameter
081 [DC Ref Hi Lmt].

Check the parameter setting.

140

DCBusLoAlarm

DC voltage is less than the value set by parameter
078 [DC Bus Lo Alarm].

Check the parameter setting.

141

DCBusHiAlarm

DC voltage exceeds the value set by parameter 079
[DC Bus Hi Alarm].

Check the parameter setting.

Table 21 - Fault/Alarm Types, Descriptions, and Actions (Continued)

No.

Name

Fa

u

lt

Alarm

Description

Action (if appropriate)

Thermal Switch 1

Thermal Switch 9

To Digital
Input 5

X52

Frame 10 LCL Filter