I/o terminal blocks – Rockwell Automation 20Y PowerFlex Active Front End User Manual
Page 42

42
Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
Chapter 1
AFE in IP20 2500 MCC Style Enclosure—Installation/Wiring
Table 5 - Recommended Control Wire for Digital I/O
Figure 20 - Door Control Box I/O Terminal Blocks and Jumpers
I/O Terminal Blocks
Table 6 - Door Control Box I/O Terminal Block Specifications for AFE in IP20 2500 MCC Style Enclosure
Type
Wire Type(s)
Description
Minimum
Insulation Rating
Unshielded
Per US NEC or applicable national or local code
—
300V, 60 °C
(140 °F)
Shielded
Multi-conductor shielded cable such as Belden
8770(or equivalent)
0.5 mm
2
(22 AWG),
3 conductor, shielded
➋
➌
J1
J2
J3
J4
J5
➍
Components mounted on inside
for location)
See
below for door control box item number descriptions and specifications.
Door Control Box Components
X3 Term. No.
Default
Description
57 and 60
—
Remote momentary pulse of 0.4…1.0 sec. across these terminals starts
precharge in REM mode when terminals 58 and 61 are remotely closed.
58 and 61
—
These terminals must be remotely closed to start precharge. Opening
these terminals opens the main contactor K1.
63 and 64
—
Remotely closing these terminals resets an AFE fault.
65 and 66
—
AFE run signal to the inverter enable input.
400 and 480
480
Control input voltage setting.
600 and 690
690
For jumper configurations,
see
.
➊
(X3 Terminals)
No.
Name
Description
Wire Size Range
(1)
(1) Maximum/minimum that the terminal block will accept - these are not recommendations.
Torque
Maximum
Minimum
Maximum
Recommended
➊
Analog I/O
Analog I/O Signals
2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.2 N•m
1.8 lb•in
0.2 N•m
1.8 lb•in
➋
Digital Inputs
Digital Input Signals
2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.2 N•m
1.8 lb•n
0.2 N•m
1.8 lb•in
➌
Digital Outputs
Digital Out Relays
2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.5 N•m
4.5 lb•in
0.5 N•m
4.5 lb•in
➍
Control Terminal
Customer input and
output control
2.5 mm
2
(14 AWG)
0.5 mm
2
(22 AWG)
0.8 N•m
7.1 lb•in
0.8 N•m
7.1 lb•in