Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

67

AFE in IP21 Rittal Enclosure—Installation/Wiring

Chapter 2

Routing the AC Input, Ground (PE), and DC Bus Output Wiring for AFE
in IP21 Rittal Enclosure

Frame 10

The AC input and ground (PE) wiring for the IP21 Rittal enclosure can be
routed through either the bottom of the enclosure, or through the bottom right
side of the enclosure (see shaded area in figure below).

The DC bus output wiring for the IP21 Rittal enclosure must be routed through
the top right side of the enclosure (see shaded area in figure below).

Figure 32 - Routing Areas for AC Input, Ground, and DC Bus Output Wiring for AFE

Frame 10 in IP21 Rittal Enclosure

Frame 13

The AC input, ground (PE), and DC bus output are located in the right-most
bay (see front view of

Figure 31

). The AC input, ground, and DC bus output

wiring can be routed through the top, bottom, or right side of the right-most bay.

ATTENTION: To minimize disruption of air flow through the enclosure and
avoid overheating within the AFE enclosure, remove only the minimum area
needed to route the power cables. In addition, remove only the minimum area
from the enclosure within the shaded areas shown in

Figure 32

for routing the

AC input, ground (PE), and DC bus output wiring. Removing sections for
routing in other areas disrupts the air flow throughout the enclosure, causing
overheating.

Area for routing
DC bus output
connections

Area for routing AC input
and ground (PE) connections

Do not allow hot
air to enter the
bottom of the enclosure