beautypg.com

Signal and control wire types, I/o terminal blocks, Signal and control wire types i/o terminal blocks – Rockwell Automation 20Y PowerFlex Active Front End User Manual

Page 73

background image

Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014

73

AFE in IP21 Rittal Enclosure—Installation/Wiring

Chapter 2

Signal and Control Wire Types

Table 14 - Recommended Signal Wire for AFE in IP21 Rittal Enclosure

Table 15 - Recommended Control Wire for Digital I/O

Figure 35 - AFE I/O Terminal Blocks and Jumpers

I/O Terminal Blocks

Table 16 - I/O Terminal Block Specifications for AFE in IP21 Rittal Enclosure

Signal Type

Wire Type(s)

Description

Minimum
Insulation Rating

Analog I/O

Belden 8760/9460
(or equivalent)

0.5 mm

2

(22 AWG), twisted pair,

100% shield with drain

(1)

(1) If the wires are short and contained within an enclosure that has no sensitive circuits, the use of shielded wire may not be necessary,

but is always recommended.

300V, 75…90 °C
(167…194 °F)

Belden 8770
(or equivalent)

0.5 mm

2

(22 AWG), 3 conductor,

shielded for remote pot only

EMC Compliance

See

CE Conformity on page 79

for details.

Type

Wire Type(s)

Description

Minimum
Insulation Rating

Unshielded

Per US NEC or applicable national
or local code

300V, 60 °C
(140 °F)

Shielded

Multi-conductor shielded cable such
as Belden 8770(or equivalent)

0.5 mm

2

(22 AWG),

3 conductor, shielded

No.

Name

Description

Wire Size Range

(1)

(1) Maximum/minimum that the terminal block will accept - these are not recommendations.

Torque

Maximum

Minimum

Maximum

Recommended

Analog I/O

Analog I/O Signals

2.5 mm

2

(14 AWG)

0.5 mm

2

(22 AWG)

0.2 N•m
1.8 lb•in

0.2 N•m
1.8 lb•in

Digital Inputs

Digital Input Signals

2.5 mm

2

(14 AWG)

0.5 mm

2

(22 AWG)

0.2 N•m
1.8 lb•n

0.2 N•m
1.8 lb•in

Digital Outputs

Digital Out Relays

2.5 mm

2

(14 AWG)

0.5 mm

2

(22 AWG)

0.5 N•m
4.5 lb•in

0.5 N•m
4.5 lb•in

J1

J2

J3

J4

J5