Rockwell Automation Publication 20Y-UM001E-EN-P - July 2014
Appendix A
Supplemental Information
Fusing and Circuit Breakers
for AFE in IP21 Rittal
Enclosure
AC Input Fuse and Circuit Breaker Ratings
The tables in this section provide the recommended AC input line fuses and
circuit breakers. The AFE in a IP21 Rittal enclosure includes the recommended
MCCB (Motor-Controlled Circuit Breaker).
400/480 Volt AC Fusing and MCCB Ratings
600/690 Volt AC Fusing and MCCB Ratings
DC Bus Output Fuse Ratings
DC Bus Output fusing must be used for short circuit protection. The tables in
this section provide the ratings of the DC Bus Output fuses used for the AFE in a
IP21 Rittal enclosure.
465-800 Volt DC Fusing
640-1100 Volt DC Fusing
Frame
Size
Fuse Ratings
MCCB Ratings
Amps
Bussman Type
(1)
(1) Suitable for replacement fuse.
Ferraz Shawmut Type
Amps
ABB Type
10
800
—
NH3UD69V800PV
630
T5H630FF3LS
1000
170M6277
—
13
2200
—
PC44UD75V22CTQ
1600
T7516FF3PR231LS
1000
(3 per phase)
170M6277
—
Frame
Size
Fuse
MCCB Ratings
Amps
Bussman Type
(1)
(1) Suitable for replacement fuse.
Ferraz Shawmut Type
Amps
ABB Type
10
700
—
PC73UD13C630PA
400
T5H400LS
700
170M6305
—
13
1800
—
PC84UD12C18CTQ
1600
T7516FF3PR231LS
700
(3 per phase)
170M6305
—
Frame
Size
Fuse
Amps
Bussman Type
(1)
(1) Suitable for replacement fuse.
Ferraz Shawmut Type
10
1100
—
PC73UD95V11CTF
1250
170M6566
—
13
2400
—
PC84UD11C24CTQ
1250
(2 per phase)
170M6566
—
Frame
Size
Fuse
Amps
Bussman Type
(1)
(1) Suitable for replacement fuse.
Ferraz Shawmut Type
10
630
—
PC73UD13C630TF
700
170M6305
—
13
2000
—
PC84UD11C20CTQ
1000
(2 per phase)
170M8510
—