SLC Ladder Logic Examples

D-3

Figure D.2 Drive 0 Control/Reference/Parameter Access Routine

Controlling the Logic Command word in the drive. B3:20/* bits are controlled elsewhere in the user program.

0

B3:20

0

Station 1
Stop
Command

N20:0

0

Station 1
Logic Command
STOP

1

B3:20

1

Station 1
Start
Command

N20:0

1

Station 1
Logic Command
START

2

B3:20

2

Station 1
Jog
Command

N20:0

2

Station 1
Logic Command
JOG

3

B3:20

3

Station 1
Clear Faults
Command

N20:0

3

Station 1
Logic Command
CLEAR FAULTS

4

B3:20

4

Station 1
Reverse
Command

N20:0

4

Station 1
Logic Command
FORWARD

5

B3:20

4

Station 1
Reverse
Command

N20:0

5

Station 1
Logic Command
REVERSE

To control the speed reference over the Profibus, the three Reference Select bits (bits 14-12) need to have the values 011.

6

N20:0

12

Station 1
Logic Command
REFERENCE SELECT 0

7

N20:0

13

Station 1
Logic Command
REFERENCE SELECT 1

8

B3:20

5

"Never Closed"

N20:0

14

Station 1
Logic Command
REFERENCE SELECT 2