Troubleshooting

8-3

MOD Status Indicator

Status

Cause

Corrective Action

Off

The adapter is not powered or
is not properly connected to
the drive.

• Securely connect the adapter to the drive

using the ribbon cable.

• Apply power to the drive (or adapter if

mounted in a DSI External Comms Kit).

Flashing
Red

The adapter has faults or a
drive is missing in Multi Drive
mode.

• Clear faults in the drive.
• Disconnect additional DSI peripheral and

cycle power to the drive (or adapter if
mounted in a DSI External Comms Kit).

• If cycling power does not correct the

problem, the adapter parameter settings
may have been corrupted. Reset defaults
and reconfigure the adapter.

• If resetting defaults does not correct the

problem, flash the adapter with the latest
firmware release.

• For Multi-Drive mode, determine which

drive is missing or faulted. Check cabling
and configuration settings (see

Configuring

the RS-485 (DSI) Network on page 7-8

).

Solid
Red

The adapter has failed the
hardware test.

• Cycle power to the drive (or adapter if

mounted in a DSI External Comms Kit).

• Replace the adapter.

Flashing
Green

The adapter is operational,
but is not transferring I/O data.

• Place the scanner in RUN mode.
• Program the controller to recognize and

transmit I/O to the adapter.

• Configure the adapter for the program in

the controller.

Solid
Green

The adapter is operational
and transferring I/O data.

No action required.