Using I/O Messaging

5-3

The Logic Command is a 16-bit word of control produced by the
controller and consumed by the adapter. The Logic Status is a 16-bit
word of status produced by the adapter and consumed by the controller.
When enabled, the Logic Command/Status word is always word 0 in the
I/O image.

This manual contains the bit definitions for compatible products
available at the time of publication in

Chapter C

,

PowerFlex 4-Class

Drives Logic Command/Status Words

. For other products, refer to their

documentation.

The Reference (16 bits) is produced by the controller and consumed by
the adapter. The Feedback (16 bits) is produced by the adapter and
consumed by the controller. When enabled, Reference/Feedback begins
at word 1 in the I/O image.

Using Logic Command/Status

Using Reference/Feedback

Size

Drive

Valid Values

(1)

(1)

The Reference/Feedback for a PowerFlex 4-Class drive is set in Hz and not in engineering units like
PowerFlex 7-Class drives. For example, “300” equates to 30.0 Hz (the decimal point is always
implied) for all PowerFlex 4-Class drives except PowerFlex 400 for which “3000” equates to 30.00
Hz. In all cases, a minus value equates to reverse motor direction, and a plus value equates to
forward motor direction.

Word in I/O Image

16-bit

PowerFlex 4 and 4M

-240.0…240.0 Hz

Word 1
(see

Figure 5.1

)

PowerFlex 40 and 40P

-400.0…400.0 Hz

PowerFlex 400

-320.00…320.00 Hz