Parameter message request – Rockwell Automation 22-COMM-P PowerFlex Profibus Adapter User Manual

Page 58

background image

6-4

Using the Parameter Messaging

Parameter Message Request

Word

Description

1

PNU - Parameter Number (Bit 0-10)
The parameter number determines which parameter to access, in the selected
peripheral. Parameters 1 - 1023 can be accessed.

Parameter numbers 1024 - 2047 are used to access the fault object. Parameter
1024 is equal to the latest fault, 1025 to the prior fault, and so on.

Bit definitions

1-1023

Parameters (Drive or Adapter)

1024

Adapter Fault Code

1025-1056

Adapter Events

1280-1289

Diagnostic Items (Single Drive)

1280-1304

Diagnostic Items (Multi Drive)

SPM - Spontaneous Message (Bit 11)
Reserved - Should always bet set to 0.

RC - Request/Response Code (Bit 12-15)
One of the following codes have to be used:

0 = No request

1 = Request parameter value

2 = Change parameter value (8-bit & 16-bit word)

3 = Spare

4 = Parameter minimum

5 = Parameter maximum

6 = default value

7 -15 = Reserved

2

IND - Index

The IND is used to specify which drive we intend to send a message

0 - 2 bits = DSI port

Bit definitions

0 0 0 Drive 0 single mode
0 0 1 Drive 0-1 multi-drive mode
0 1 0 Drive 0-2 multi-drive mode
0 1 1 Drive 0-3 multi-drive mode
1 0 0 Drive 0-4 multi-drive mode
1 0 1 Adapter

3 - 15 = Reserved

3

PVA - Parameter value
Spare

4

PVA - Parameter value (8-bit & 16-bit word)
Read Request: Not used
Write Request: Contents the write value for a 8-bit or 16-bit parameter.