Troubleshooting

PORT Status Indicator

Status

Cause

Corrective Action

Off

The adapter is not powered
or is not properly connected
to the drive.

• Securely connect the adapter to the drive

using the ribbon cable.

• Apply power to the drive (or adapter if

mounted in a DSI External Comms Kit).

Flashing
Red

In Single mode, the adapter
is not receiving a ping
message from the drive.

In Multi-Drive mode, the
adapter is not receiving a
ping message from the
drive—or the adapter is
connected to a drive that is
not compatible.

• Verify that the Mode Jumper J2 (

Figure 2.1

)

is in the position corresponding to the mode
in which the adater is being used.

• Verify the setting for Parameter 11 - [DSI

I/O Cfg].

• Verify that cables are securely connected

and not damaged. Replace cables if
necessary.

• Cycle power to the drive (or adapter if

mounted in a DSI External Comms Kit).

• Connect the adapter to compatible

PowerFlex 4-Class drive.

Solid
Red

The drive has refused an I/O
connection from the adapter.

Another DSI peripheral is
using the same DSI port as
the adapter.

Important: Cycle power to the drive (or adapter
if mounted in a DSI External Comms Kit) after
making the following corrections:
• Verify that all DSI cables are securely

connected and not damaged. Replace
cables if necessary.

• Check the Events, replace the adapter with

a compatible Allen-Bradley branded product
(22-COMM-P).

Flashing
Green

Not used.

Solid
Green

The adapter is properly
connected and is
communicating with the
drive.

No action required.

Solid
Orange

The adapter is booting.

Wait until boot program has been finished.

Flashing
Orange

The adapter is in flash mode
(SW8 down).

Application failure.

• Wait until Firmware Update has been

finished, then switch SW8 to 1.

• Download Application code.