Adapter Parameters

14

[Flt Cfg Ref]

Sets the Reference data that is sent to the drive if
any of the following is true:
Parameter 09- [Comm Flt Action] is set to

Send Flt Cfg and communications are
disrupted.

Parameter 10 - [Idle Flt Action] is set to

Send Flt Cfg and the scanner is put into
Program mode.

Default:

0

Minimum:

0

Maximum:

4000

Type:

Read/Write

Reset Required:

No

Important: If the drive uses a 16-bit
Reference, the most significant word of this
value must be set to zero (0) or a fault will
occur.

15

Reserved

16

Reserved

17
18
19
20
21

[Drv 0 Addr]
[Drv 1 Addr]
[Drv 2 Addr]
[Drv 3 Addr]
[Drv 4 Addr]

Sets the corresponding node addresses of the
daisy-chained drives when the adapter Mode
Jumper (J2) is set for Multi-Drive operation.

Important: The settings for these parameters
must match the drive Parameter A104 - [Comm
Node Addr] settings in the respective drives. Each
setting must also be unique (no duplicate node
address).

Default:

1

Default:

2

Default:

3

Default:

4

Default:

5

Minimum:

1

Maximum:

127

Type:

Read/Write

Reset Required:

Yes

24

[P-DP State]

Displays the state of the Profibus controller.

0 = Not connected to the network.
1 = On network and not scanning or not connected

to the network

2 = Online/running
3 = Error in configuration

Default:

N/A

Values:

0 = WAIT_PRM
1 = WAIT_CFG
2 = DATA_EX
3 = ERROR

Type:

Read Only

Parameter

No. Name and Description

Details