Rockwell Automation 22-COMM-P PowerFlex Profibus Adapter User Manual
Page 84
B-4
Adapter Parameters
14
[Flt Cfg Ref]
Sets the Reference data that is sent to the drive if
any of the following is true:
• Parameter 09- [Comm Flt Action] is set to
Send Flt Cfg and communications are
disrupted.
• Parameter 10 - [Idle Flt Action] is set to
Send Flt Cfg and the scanner is put into
Program mode.
Default:
0
Minimum:
0
Maximum:
4000
Type:
Read/Write
Reset Required:
No
Important: If the drive uses a 16-bit
Reference, the most significant word of this
value must be set to zero (0) or a fault will
occur.
15
Reserved
—
16
Reserved
—
17
18
19
20
21
[Drv 0 Addr]
[Drv 1 Addr]
[Drv 2 Addr]
[Drv 3 Addr]
[Drv 4 Addr]
Sets the corresponding node addresses of the
daisy-chained drives when the adapter Mode
Jumper (J2) is set for Multi-Drive operation.
Important: The settings for these parameters
must match the drive Parameter A104 - [Comm
Node Addr] settings in the respective drives. Each
setting must also be unique (no duplicate node
address).
Default:
1
Default:
2
Default:
3
Default:
4
Default:
5
Minimum:
1
Maximum:
127
Type:
Read/Write
Reset Required:
Yes
24
[P-DP State]
Displays the state of the Profibus controller.
0 = Not connected to the network.
1 = On network and not scanning or not connected
to the network
2 = Online/running
3 = Error in configuration
Default:
N/A
Values:
0 = WAIT_PRM
1 = WAIT_CFG
2 = DATA_EX
3 = ERROR
Type:
Read Only
Parameter
No. Name and Description
Details