5-2

Using I/O Messaging

The Profibus specification requires that the terms input and output be
defined from the scanner’s point of view. Therefore, Output I/O is data
that is output from the scanner and consumed by the Profibus adapter.
Input I/O is status data that is produced by the adapter and consumed as
input by the scanner. The I/O image table will vary based on the:

• Configuration of the Mode Jumper (J2) on the adapter and

Parameter 11 - [DSI I/O Cfg]. The image table always uses
consecutive words starting at word 0.

Figure 5.1

illustrates an example of an I/O image (16-bit words) for the

adapter operated in Single mode.

Figure 5.1 Example of I/O Image for Adapter in Single Operating Mode

Single operating mode is the typical configuration, where one node
consists of a PowerFlex 40, PowerFlex 40P or PowerFlex 400 drive with
a 22-COMM-P adapter.

For Multi-Drive mode, where one node can consist of up to 5 drives,
refer to

Chapter 7

,

Using Multi-Drive Mode

.

Understanding the I/O Image

Controller

Scanner

Adapter

PowerFlex

4-Class Drive

Profibus

DSI

Output
Image
(Write)

Input
Image
(Read)

Message

Handler

Message

Buffer

0 Logic Status
1 Feedback

Logic Status
Feedback

Word and I/O

Message

Handler

0 Logic Command
1 Reference

Logic Command
Reference