C13885 | clear process data, C13887 | suppress signalling diag. mess. upon, C13899 | station name – Lenze E84AYCER User Manual
Page 86: C13885, C13864, C13899, E84aycer communication manual (profinet)
E84AYCER communication manual (PROFINET)
Parameter reference
Parameters of the communication module
86
L
EDS84AYCER EN 2.0 - 11/2010
C13885
C13887
C13899
Parameter | Name:
C13885 | Clear process data
Data type: UNSIGNED_8
Index: 10690
d
= 29C2
h
This code is used to set the process data that are to be processed by the IO device in order to maintain internal
communication when the PROFINET has left the DATA_EXCHANGE status.
Selection list
(Lenze setting printed in bold)
Information
0 Use of most recent master PDOs
The last data sent by the IO controller are used.
1 PDOs are set to the value'0'
The contents of the process data are set to the value "0".
;
Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13887 | Suppress signalling diag. mess. upon
Data type: BITFIELD_8
Index: 10688
d
= 29C0
h
This code serves to inhibit the transmission of alarm messages to the IO controller. By this, errors of a specific type
can be systematically suppressed. All errors are furthermore entered in the logbook.
• A change will only become effective immediately if no error number with the error type selected here is pending
in C00165.
Value is bit-coded:
Information
Bit 0 Fault
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
;
Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13899 | Station name
Data type: VISIBLE_STRING
Index: 10676
d
= 29B4
h
The name with a max. length of 240 characters is distributed to the subindices. The name can be entered starting
with subindex 1. The following unused subindices are not relevant.
• The station name must be assigned in accordance with the PROFINET specification. In the standard setting a
deleted name is displayed. The name is also deleted if the "Reset to factory defaults" command is executed by an
IO supervisor or an IO controller.
• A change of the station name will only become effective by switching the mains of the controller.
Setting the station name ( 36)
Subcodes
Lenze setting
Information
C13899/1
1st ... 30th character
C13899/2
31st ... 60th character
C13899/3
61st ... 90th character
C13899/4
91st ... 120th character
C13899/5
121st ... 150th character
C13899/6
151st ... 180th character
C13899/7
181st ... 210th character
C13899/8
211th ... 240th character
;
Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT