2 possible causes and remedies, Profinet: exist. conn. to 8400 lost [0x01bc3100, Profinet: memory: no access [0x01bc5531 – Lenze E84AYCER User Manual
Page 74: Profinet: memory: read error [0x01bc5532, Profinet: memory: write error [0x01bc5533, Possible causes and remedies, 0x01bc3100, 0x01bc5531, 0x01bc5532, 0x01bc5533

E84AYCER communication manual (PROFINET)
Error messages
Possible causes and remedies
74
L
EDS84AYCER EN 2.0 - 11/2010
12.2
Possible causes and remedies
In this chapter, all error messages of the communication module are listed in numerical
order of the error numbers. Possible causes and remedies and responses to the error
messages are described in detail.
Tip!
You will find a list of all error messages of the communication module in
alphabetical order in the previous chapter "
Short overview (A-Z) of the PROFINET
PROFINET: Exist. conn. to 8400 lost [0x01bc3100]
PROFINET: Memory: No access [0x01bc5531]
PROFINET: Memory: Read error [0x01bc5532]
PROFINET: Memory: Write error [0x01bc5533]
Response (Lenze setting in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
• Network cable (plug) is defective.
• Network cable at PROFINET terminal X256 or X257 is
disconnected.
• Voltage supply is interrupted.
Check cables and connections.
Plug in network cable at PROFINET terminal X256 or
X257.
Response (Lenze setting in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Memory could not be accessed.
Send device with error description to Lenze.
Response (Lenze setting in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Parameter could not be read.
Send device with error description to Lenze.
Response (Lenze setting in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Parameter could not be written.