beautypg.com

E84aycer communication manual (profinet) – Lenze E84AYCER User Manual

Page 33

background image

EDS84AYCER EN 2.0 - 11/2010

L

33

E84AYCER communication manual (PROFINET)

Installation

Electrical installation

Assignment of the X255 plug connector

Terminal data

Designation

Description

+

V = 24 V DC (20.4 V - 0 % ... 28.8 V + 0 %)

I = 140 mA

-

Reference potential for the external voltage supply

Field

Values

Electrical connection

2-pole plug connector with spring connection

Possible connections

Rigid:

0.2 ... 1.5 mm

2

(AWG 24 ... 16)

Flexible:

Without wire end ferrule

0.2 ... 1.5 mm

2

(AWG 24 ... 16)

With wire end ferrule, without plastic sleeve

0.2 ... 1.5 mm

2

(AWG 24 ... 16)

With wire end ferrule, with plastic sleeve

0.2 ... 1.5 mm

2

(AWG 24 ... 16)

Stripping length

10 mm