E84AYCER communication manual (PROFINET)
Commissioning
Setting the station name
36
L
EDS84AYCER EN 2.0 - 11/2010
6.3
Setting the station name
The station name ...
is required for unambiguous addressing of the Inverter Drive 8400 by the IO controller.
can either be assigned by the IO controller via PROFINET or set manually in the
»Engineer«.
has to be allocated in accordance with the PROFINET specification:
– 1 or several labels separated by ".".
– Max. length per label: 63 characters
– Max. total length: 240 characters
– Permissible characters: [a ... z], [0 ... 9], [.], [-]
– Labels must not begin or end with [-].
Prohibited syntax:
– "n.n.n.n" (n = 0 ... 999)
– "port-xyz" (x, y, z = 0 ... 9)
– "port-xyz-abcde" (a, b, c, d, e, x, y, z = 0 ... 9)
Note!
• The PROFINET function by means of which an accessible device can be
identified is supported. During execution of the function the red LED "ME"
• In the case of impermissible settings the red LED "BE" (
) blinks. The communication module then continues to operate with the
deleted name. Operation on the PROFINET requires a valid station name.
• If the station name is assigned by the IO controller via PROFINET the change
is activated immediately. The current station name is displayed in code
.