Commissioning

Setting the station name

36

L

EDS84AYCER EN 2.0 - 11/2010

6.3

Setting the station name

The station name ...

 is required for unambiguous addressing of the Inverter Drive 8400 by the IO controller.
 can either be assigned by the IO controller via PROFINET or set manually in the

»Engineer«.

 has to be allocated in accordance with the PROFINET specification:

– 1 or several labels separated by ".".
– Max. length per label: 63 characters
– Max. total length: 240 characters
– Permissible characters: [a ... z], [0 ... 9], [.], [-]
– Labels must not begin or end with [-].

 Prohibited syntax:

– "n.n.n.n" (n = 0 ... 999)
– "port-xyz" (x, y, z = 0 ... 9)
– "port-xyz-abcde" (a, b, c, d, e, x, y, z = 0 ... 9)

Note!

• The PROFINET function by means of which an accessible device can be

identified is supported. During execution of the function the red LED "ME"

blinks (

Module status displays

( 67)

.

• In the case of impermissible settings the red LED "BE" (

Fieldbus status displays

( 68)

) blinks. The communication module then continues to operate with the

deleted name. Operation on the PROFINET requires a valid station name.

• If the station name is assigned by the IO controller via PROFINET the change

is activated immediately. The current station name is displayed in code

C13864

.