4 transmitter setup template, Transmitter setup template -17 – CiDRA SONARtrac PW VF-100 User Manual
Page 191

20835-01 Rev 04
Page 9-17
Direction arrow on the band opposite the actual flow direction
within the pipe or the process flow has changed direction) press
the ‘ENTER’ key and toggle the ↑ or ↓ to change flow direction.
Once changed press the
‘ENTER’ key.
The display will show ‘→Flow Direction’ on Line 2. Press the ↓
key
to scroll to ‘OP Mode’. If ‘Flow/GVF/SOS’ is not displayed,
press the ‘ENTER’ key and then scroll using the ↓ key to select
‘Flow/GVF/SOS’. Then press the ‘ENTER’ key.
Press the
↓ key to scroll to ‘→Set Date/Time’ on Line 2. Press the
‘ENTER’ key and the current saved date and time will be displayed
on Line 4 of the display. Use the arrow keys (
↑ and ↓ to scroll
through the values and
← and → to change character) to enter the
date and time. Note: Time is in 24 hour format. Once the date
and time have been set press the
‘ENTER’ key.
Press the
↓ key to scroll to ‘→Set Date Format’ on Line 2. Press
the ‘ENTER’ key and the current date format will be displayed on
Line 4 of the display. Use the arrow keys (
↑ and ↓) to scroll to the
desired format. Press the
‘ENTER’ key to set the desired date
format
followed by the ‘BACK’ key.
At this point ‘Basic Config’ is displayed on Line 1 of the display.
The user can re-enter this menu if desired by pressing the
‘ENTER’ key or by pressing the ↑ or ↓ arrows to move to other
Level 1 menus.
Press the ‘EXIT’ key to return to ‘Operational Mode’.
Entry of inputs to the other Level 1 menus is by the same process as
used in ‘Basic Config’.
9.4.4
Transmitter Setup Template
The following table provides a template for recording the transmitter
setup for future reference. Additionally, a Data Snapshot (refer to
Section 10) should be taken and kept on file. The Data Snapshot
should be obtained with the passive sonar meter system configured
and the process operating at normal conditions.