CiDRA SONARtrac PW VF-100 User Manual
Page 124

20833-01 Rev 04
Page 7-30
Table 10 (page 6)
VF Transmitter Menu Tree Software Release 04.02`.XX
Level 1
Level 2
Level 3
Range
Description
Communications
Ethernet
IP Address
0.0.0.0 to
255.255.255.255
Current IP address
Subnet Mask
0.0.0.0 to
255.255.255.255
Current Subnet Mask
Front Panel
Serial
Baud Rate
2400 to 115200
Serial baud rate for front
panel serial port
Internal
Serial
Config
RS232 or RS485
Serial communications
protocol type
Baud Rate
2400 to 115200
Serial baud rate for
internal serial port
Data Bits
8, 7
Internal RS232/RS485
serial port data bits
Parity
Even, odd, none
Internal RS232/RS485
serial port parity
Stop bits
1 or 2
Internal RS232/RS485
serial port stop bits
HART
Preambles
5 - 20
# Preamble chars
ahead of MSG
Resp.
Preambles
5 - 20
# Preambles in
response from
transmitter. Change to
match HART
communicator
Univ. Cmd.
Rev.
5 or 6
Major protocol Revision
5, or Revision 6
Polling
Address
0 - 15
Non-zero for multi-drop
connections
=0 for single connection
Find Device
Arm
Enable, Disable
When ‘Enabled”, makes
transmitter respond to
HART “Find Device”
command
MODBUS (if
ON
– No
Fieldbus)
Mode
RTU, ASCII
Transmission mode
select
Address
001-247
Device address select
ASCII
Timeout
04-99
ASCII timeout select
Reset
Comms
Resets communications
ports without re-booting
transmitter