Table 12 (page 6) VF/GVF Transmitter Menu Tree Software Release 04.02.XX
Level 1
Level 2
Level 3
Range
Description
Customize
Display
Line 1
Flow Rate, Totalizer,
Flow Rate %GVF, SOS,
True Liquid Flow, Blank
Parameter displayed on
line 1
Line 2
Flow Rate, Totalizer,
Flow Rate %GVF, SOS,
True Liquid Flow, Blank
Parameter displayed on
line 2
Contrast
0 to 1000 (default 170)
Contrast of display
Sensor Setup
State
On/off
Enable / disable each
sensor
Flow Units
Volume
gal, l, m
3
, user, ft
3
, igal,
ft, m
Flow units
Time
d, h, m, s, user
Time units
User Vol Label User defined
Custom flow vol label
Use Vol Base
gal, l, m
3
, ft
3
, igal, ft, m
Base units for custom
volume label
User Vol Scale
0.0000 e-38 to
9.9999 e+38
Scale factor on custom
volume base
User Time
Label
User defined
Custom time label
User Time
Base
d, h, m, s
Base units for custom
time label
User Time
Scale
0.0000 e-38 to
9.9999 e+38
Scale factor on custom
time base
SOS Units
Units
Feet or meters
Units of measure
Flow Cutoff
Range
Low End
0% to 100% (3 to 30
ft/s)
Under this value ‘
High End
0% to 100% (3 to 30
ft/s)
Over this value ‘>max
flow’ will be displayed
Totalizer
Units
gal, l, m
3
, ft
3
, user def
Units for totalizer
Lowcut Enable Enable, Disable
Turns totalizer lowcut
on / off
Lowcut
0% to 100% (3 to 30
ft/s)
Flow values below this
not used for totalizer
Multiplier
M, k, 1
Total Multiplier
Reset
Reset totalizer value
Input
Vol Flow
Totalized flow basis
Wr Protect
Mode
Enable, Disable
When enabled no other
parameters can be
changed