CiDRA SONARtrac PW VF-100 User Manual
Page 137

20833-01 Rev 04
Page 7-43
Table 12 (page 3) VF/GVF Transmitter Menu Tree Software Release 04.02.XX
Level 1
Level 2
Level 3
Range
Description
Output Config
4-20mA
Ch1& Ch2
Output Sel
SOS, GVF, Flow Rate,
True Liquid Flow, SOS
Quality, Flow Quality,
Blank
Parameter to output
Power Sel
Internal, External
Power supply for 4-
20mA current
Low End
Based on ‘output sel’
Low end output (4mA)
High End
Based on ‘output sel’
High end output (20mA)
Out of Range
Hold, >20mA, <4mA,
4mA
Behavior when meter
reading is out of range
or meter has no reading
Overrange
Rail
Enable, Disable
‘Enable’ causes the
output to go to full
(20mA) or min (4mA)
when system over
ranges
4mA Trim
2 to 6
Adjust 4mA output
20mA Trim
18 to 22
Adjust 20mA output
Pulse
Multiplier
0 - 999999
Multiplier on output
Width (ms)
.5,1,20,33,50,100
Pulse width
Lowcut
0 % to 100 %
Low end cutoff
Output Sel
GVF, SOS, Flow Rate,
True Liquid Flow, Flow
Quality, SOS Quality
Parameter to output
Alarm
Control
Warning
Off/On
Activates alarm warning
function
Critical
0 % to 100 % Off/On
Activates alarm critical
function
Manual Clear Enable/Disable
Allows for manual or
automatic alarm
clearing
Alarm
Warning
Threshold
Flw Min
0-100% of range
Off/On/Equation Input
Used to set the
minimum and maximum
values for a warning
alarm
GVF Min
Flw Max
GVF Max
Alarm Critical
Threshold
Flw Min
0-100% of range
Off/On/Equation Input
Used to set the
minimum and maximum
values for a critical
alarm
Flw Max
GVF Min
GVF Max