beautypg.com

Set error outputs, Chemical purge (optional), General – Vaisala HMT310 User Manual

Page 57

background image

Chapter 4 _________________________________________________________________ Operation

VAISALA ________________________________________________________________________ 57

Set Error Outputs

Syntax: AERR

The factory default state for analog outputs during error condition is

0 mA. Be careful when selecting the new error value, the error state of

the transmitter should not cause problems in process monitoring.

Example:

>aerr

Ch1 error out : 0.000mA ?

Ch2 error out : 0.000mA ?

NOTE

Error output value needs to be within the valid range of the output type.

NOTE

The error output value is shown only when there are minor electrical

faults such as a humidity sensor open circuit. When there is a severe

device malfunction, such as an analog output electronics failure or a

microprocessor ROM/RAM failure, the error output value is not

necessarily shown.

Chemical Purge (Optional)

General

In some specific applications the sensor gain may decrease gradually due

to an interference caused by some particular chemical present in the

ambient (see Figure 16 on page 58). The sensor polymer absorbs the

interfering chemical; this reduces the ability of the polymer to absorb

water molecules and so decreases the sensor gain. In chemical purge, the

humidity sensor is heated to a temperature level of approximately

+180 °C for several minutes, which evaporates the interfering chemical.

The purge function starts with a heating stage, continues with a settling

stage, and when the temperature of the sensor is decreased, the

transmitter returns to normal mode. The whole cycle takes about 8

minutes.

NOTE

The chemical purge function locks the output values for about 8 minutes.