beautypg.com

Output reading once, Set serial interface mode, Serial line settings – Vaisala HMT310 User Manual

Page 43: On set serial, Interface mode

background image

Chapter 4 _________________________________________________________________ Operation

VAISALA ________________________________________________________________________ 43

Output Reading Once

Syntax in STOP mode: SEND

Syntax in POLL mode: SEND aa

Where
aa = Address of the transmitter when more than one transmitter is

connected to a serial bus (0 ... 99).

Set Serial Interface Mode

Syntax: SMODE x

Where
x

= STOP/RUN/POLL

STOP mode: Transmitter in standby for serial

commands

RUN mode: Transmitter outputs data continuously

POLL mode: Transmitter only responds to

addressed command

Example:

>smode run

Output mode : RUN

>smode stop

Output mode : STOP

Serial Line Settings

Syntax: SERI b p d s

Where
b = bauds (300, 600, 1200, 2400, 4800, 9600,19200)

p = parity (n = none, e = even, o = odd)

d = data bits (7 or 8)

s = stop bits (1 or 2)

The settings can be changed one parameter at a time or all parameters at

once.