Setting, scaling and testing analog outputs, Set analog output mode, Select parameter for analog outputs – Vaisala HMT310 User Manual
Page 54: Setting, scaling, And testing analog outputs

User's Guide _______________________________________________________________________
54 ___________________________________________________________________ M210619EN-E
Setting, Scaling and Testing Analog Outputs
Set Analog Output Mode
Syntax: AMODE ch1 ch2
Where
ch1 and ch2
= I0 = 0 ... 20 mA
I1 = 4 ... 20 mA
U1 = 0 … 5 V *
U2 = 0 … 10 V *
*) Voltage output applicable from software version 2.0.1 onward.
Example:
>amode i1 i1
Ch1 output mode: 4...20mA
Ch2 output mode: 4...20mA
>
NOTE
1 … 5 V output can be selected when ordering the device. The 1 ... 5 V
output is based on the 0 … 5 V output mode, but has been adjusted to
1 … 5 V by scaling the valid range to 1 … 5. In the scaled 1 … 5 V
output mode, 0 V is reserved for error output (AERR set to 0).
Select Parameter for Analog Outputs
Syntax: ASEL xxx yyy
Where
xxx =
Quantity of channel 1
yyy =
Quantity of channel 2
After entering the command, the low and high values of each channel are
displayed one row at a time and a new value can be entered. Enter a new
value and press
entering a value to keep the current setting.
Use the abbreviations shown in Table 17 on page 55.