Appendix B: HP SNMP events 58
Trap types
Rules file Description
Netcool
severity
cpqRPMtrapUPSTemperatureOut
OfRange (21007)
21007
This event occurs when a UPS device
reports temperature is out of range.
Critical (5)
cpqRPMtrapUPSTemperatureOut
OfRangeCleared (21008)
21008
This event occurs when a UPS device
reports temperature is normal.
Clear (0)
cpqRPMTrapUPSShutdownPendi
ng (21011)
21011
This event occurs when a UPS device
reports a shutdown pending condition.
Major (4)
cpqRPMTrapUPSShutdownPendi
ngCleared (21012)
21012
This event occurs when a UPS device
reports a shutdown pending condition is
cleared.
Clear (0)
cpqRPMTrapUPSShutdownImmin
ent (21013)
21013
This event occurs when a UPS device
reports a shutdown imminent condition.
Critical (5)
cpqRPMTrapUPSShutdownImmin
entCleared (21014)
21014
This event occurs when a UPS device
reports a shutdown imminent condition is
cleared.
Clear (0)
cpqRPMtrapUPSOutputoutofRan
ge (21019)
21019
This event occurs when a UPS device
reports output voltage is out of range.
Critical (5)
cpqRPMTrapUPSOutputVoltage
Normal (21020)
21020
This event occurs when a UPS device
reports output voltage is normal.
Clear (0)
cpqRPMtrapUPSInputOutofRang
e (21021)
21021
This event occurs when a UPS device
reports input voltage is out of range.
Major (4)
cpqRPMtrapUPSInputOutofRang
eCleared (21022)
21022
This event occurs when a UPS device
reports input voltage is normal.
Clear (0)
cpqRPMTrapUPSLossOfRedunda
ncy (21023)
21023
This event occurs when a UPS device
reports a loss of redundancy.
Major (4)
cpqRPMTrapUPSLossOfRedunda
ncyCleared (21024)
21024
This event occurs when a UPS device
reports a loss of redundancy cleared or
configuration changed from N+1 to
Capacity.
Clear (0)
cpqRPMTrapUPSOnBuck
(21029)
21029
This event occurs when a UPS device
reports an On Buck condition.
Minor (3)
cpqRPMTrapUPSOnBoost
(21031)
21031
This event occurs when a UPS device
reports an On Boost condition.
Minor (3)
cpqRPMTrapUPSManualLoadDu
mped (21033)
21033
This event occurs when the UPS is powered
off with user interaction.
Major (4)
cpqRPMTrapUPSManualLoadDu
mpedCleared (21034)
21034
This event occurs when a UPS device
reports UPS output is restored.
Clear (0)
cpqRPMTrapUPSFanFailure
(21035)
21035
This event occurs when a UPS device
reports a fan failure.
Critical (5)
cpqRPMTrapUPSFanFailureClear
ed (21036)
21036
This event occurs when a UPS device
reports a fan failure is cleared.
Clear (0)
cpqRPMTrapUPSEPOInitiated
(21037)
21037
This event occurs when a UPS device
reports an Emergency Power Off (EPO)
command was received to shutdown the
UPS immediately. This command might
come from a local control panel or from a
remote source.
Critical (5)