Appendix B: HP SNMP events 54
Rack and power management (CPQRPM.MIB)
Trap types
Rules file Description
Netcool
severity
cpqRPMTrapDeviceConnected
(1)
1
This event occurs when Device is
connected.
Clear (0)
cpqRPMTrapConnectionLost (2) 2
This event occurs when Connection is lost. Critical (5)
cpqRPMTrapLookupFailed (3)
3
This event occurs when CRPM failed to find
an IP address for the device hostname.
Critical (5)
cpqRPMTrapConnectionFailed
(4)
4
This event occurs when CRPM failed to
connect to a drive.
Critical (5)
cpqRPMTrapDeviceSettingsChan
ged (5)
5
This event occurs when Device settings is
changed by a user.
Minor (3)
cpqRPMTrapCMCTemp1Below
Min(10001)
10001
This event occurs when a CMC device
reports temperature 1 is below minimum
threshold.
Major (4)
cpqRPMTrapCMCTemp1Above
Warn(10002)
10002
This event occurs when a CMC device
reports temperature 1 is above Minor (3)
threshold.
Minor (3)
cpqRPMTrapCMCTemp1Above
Max(10003)
10003
This event occurs when a CMC device
reports temperature 1 is above maximum
threshold.
Major (4)
cpqRPMTrapCMCTemp1Normal
(10004)
10004
This event occurs when a CMC device
reports temperature 1 has returned to
normal.
Clear (0)
cpqRPMTrapCMCTemp2Below
Min(10005)
10005
This event occurs when a CMC device
reports temperature 2 is below minimum
threshold.
Major (4)
cpqRPMTrapCMCTemp2Above
Warn(10006)
10006
This event occurs when a CMC device
reports temperature 2 is above Minor (3)
threshold.
Minor (3)
cpqRPMTrapCMCTemp2Above
Max(10007)
10007
This event occurs when a CMC device
reports temperature 2 is above maximum
threshold.
Major (4)
cpqRPMTrapCMCTemp2Normal
(10008)
10008
This event occurs when a CMC device
reports temperature 2 has returned to
normal.
Clear (0)
CpqRPMTrapCMCVoltUnder(10
011)
10011
This event occurs when a CMC device
reports voltage is below minimum
threshold.
Major (4)
CpqRPMTrapCMCVoltOver(100
12)
10012
This event occurs when a CMC device
reports voltage is above maximum
threshold.
Major (4)
CpqRPMTrapCMCVoltNormal(1
0013)
10013
This event occurs when a CMC device
reports voltage has returned to normal.
Clear (0)
CpqRPMTrapCMCHmdtUnder(1
0021)
10021
This event occurs when a CMC device
reports humidity is below minimum
threshold.
Major (4)