Show enclosure status, Show enclosure temp – HP Onboard Administrator User Manual
Page 126

Enclosure management commands 126
Spare Part Number: XXXXXX-001
Product Ver:
Diagnostic Status:
Internal Data OK
Device Failure OK
Power Cord OK
SHOW ENCLOSURE STATUS
•
Command:
SHOW ENCLOSURE STATUS
•
Description:
Displays the basic health and status of the enclosure subsystem
•
Access level/Bay level:
All
•
Restrictions:
None
•
Example:
OA-0018FE27577F> SHOW ENCLOSURE STATUS
Enclosure:
Status: OK
Unit Identification LED: Off
Diagnostic Status:
Internal Data OK
Onboard Administrator:
Status: OK
Power Subsystem:
Status: OK
Power Mode: Not Redundant
Power Capacity: 3600 Watts DC
Power Available: 2685 Watts DC
Present Power: 463 Watts AC
Cooling Subsystem:
Status: OK
Fans Good/Wanted/Needed: 6/6/5
Fan 1: 9497 RPM (53%)
Fan 2: 7342 RPM (41%)
Fan 3: 9493 RPM (53%)
Fan 4: 9495 RPM (53%)
Fan 5: 7343 RPM (41%)
Fan 6: 9508 RPM (53%)
SHOW ENCLOSURE TEMP
•
Command:
SHOW ENCLOSURE TEMP
•
Description:
Displays the highest ambient temperature being reported by the installed blade devices. If no blade
devices are installed, displays the temperature of the OA module as an approximation of the ambient
temperature.