10.4 Extra batching options

10.4.1 Air buoyancy correction

If this option is enabled, at the end of the batch the Air buoyancy correction is calculated and possible

printed on the ticket (registers 527…529).

CLNT0300.DAT Excerpt

10.4.2 Batching without printer

The option to use batching without use of the printer. The tickets are saved in the UFP. If a printer is

connected, the tickets will be printed. If there is no printer available, no alarm or window swapping will

take place.

12.05 Modbus_control c=#2 //0=No Control batching through Modbus

//1=Control batching through Modbus

//2=as 0 with no printer alarm

//3=as 1 with no printer alarm

19 [WEIGHT OF STANDARD (batch) VOLUME IN AIR (AirBuoyancy correction)]

The weight (in air) is calculated as follows:

W.I.A. = Volume(15) * ( Density(15) + AirBuoyancy ) * Factor + Offset

[kg] = [m3] * ( [kg/m3] + [kg/m3] )

Where the * Factor + Offset part is to be able to influence the unit of

the W.I.A. Ie. a factor of 0.001 will give the W.I.A. in metric tons [t].

19.01 WeightInAir

=#0

//[0..1] 0=OFF, 1=ON

19.02 AirBuoyancy

=#-1.10

//[-100..100] Air Buoyancy number [kg/m3]

19.03 Factor

=#0.001

//19.3 and 19.4 are for calculating the desired

19.04 Offset

=#0.000

//unit by utilising: Y = X * Factor + Offset