ALTOSONIC V

Operating Manual rev02 E

7.30850.34.00

Page 70 of 106

Now batch is ready to start by Function key F10 or by Modbus command if enabled. Note that

depending on security level it is only possible to start a batch if flow is at zero flow conditions

Possible to cancel the set-up (F2)

Or return to the API settings (F3) or the Text settings (F4)

6.9

Batch start

Starting a batch holds the following automatic actions:

Reset of: errors, resetable totalisers and batch flow-weighted averages (temp, press, densities

etc.)

Increase ticket number by one (is saved in the “batch status” file.

Saving of all batch parameters (for later use when batch is stopped and certain batch start values

are requested on ticket) in a “batch start” file that is secured by a CRC-checksum

New since software version 03.00.50.01 is the option to view, during the batch, the worst case batch

Volume Error % estimate due to batch alarms such as path failures, input signals alarms etc etc