6.3.1
Special characters for printer control:
Special characters for printer control start with a 3.
The so called escape codes for printer control can be inserted into the Ticket Layout
Examples:
~3007@
Printer sounds a bel
~3012@
Formfeed
~3027@~3067@~3000@~30xx@
Set page length in inch in ~30xx@: xx=1…22
~3027@~3067@~3000@~3xxx@
Set page length in lines in ~3xxx@: xx=1…127
~3027@~3087@~3049@
Select double sized characters
~3027@~3087@~3048@
Cancel double sized characters
~3027@~3071@
Select double strike printing
~3027@~3072@
Cancel double strike printing
~3027@~3052@
Select italic characters
~3027@~3053@
Cancel italic characters
~3027@~3054@
Cancel italic characters
~3027@~3057@
Enable paper out sensor
~3027@~3056@
Disable paper out sensor
6.4
Initial batch set-up
The initial batch set-up is by initialisation file CLNT0300.dat file under section 12:
\
•
There are 4 modes for Batch configuration:
BATCHING
ON
Start stop batch
permission
Confirmation asked
on batch settings
API settings during
batch possible
0
Batch mode disabled
-------
------
1
Only at zero flow
conditions
Yes
No
2
At all flowing conditions
Yes
No
12
Only in use when a Epson Serial Printer according DIN66258 standard
is connected.
Note that in the HSET0300.UFP file (for hardware setup) the following data
must be set:
-1.4 Location_stat must be enabled (saving of status)
-1.8 Location_tic must be a disk with enough storage capacity
12.1 BATCHING_ON c=#2
//0=Internal batching disabled
//Manual batching modes:
//1=Enable Batching (start stop at zero flow)
//2=Enable Batching (start stop at all flows)
//Continuous piipe line modes
//3=Enable Batching: (Automatic)
//4=Enable Batching: (No Reset,possibly forced reset)
//If enabled then automatic initialize printer
12.2 Max_tickets c=#100
//Maximum number of last tickets saved 10..100000
//depending on disk space (see Location_tic above)
12.3 Hour_start c=#10
//Start hour 0..23 for continous pipe line ticket
12.4 Hour_interval c=#1
//Interval hour 1..24 for continous pipe line ticket
//0=No tickets automatically, only on demand
12.5 Modbus_control c=#1
//0=No Control batching through modbus
//1=Control batching through modbus
//2=as 0 with no printer alarm on printer failure
//3=as 1 with no printer alarm on printer failure