beautypg.com

6 basic operation> 6-4 – Yokogawa Extractive Oxygen Gas Analyzer TDLS220 User Manual

Page 34

background image

<6 BASIC OPERATION> 6-4

IM 11Y01B02-01E-A 4th Edition September 11, 2012-00

Optional “Mini-Display 4 line x 20 character” Software Map

Display Text

Description

Line 1 - Measurement

O2 xx.x %

Measured gas and unit of measurement

Line 2 – Transmission or Sec-

ond Gas Measurement

Transmission xx.x %

Laser light transmission strength

(0-100% range)

CH4 xx.x %

Second measurement gas and unit

Line 3 - Status

Initializing……

shown during the power-up and initialization of the

analyzer

System OK

Normal Operation condition with no active alarms

WARNING Det Sig Low

WARNING Conditions

WARNING Trans Low

WARNING Spectr Noise

WARNING Gas Pres

WARNING Gas Temp

WARNING Gas Level

WARNING Board Temp

WARNING Val Failure

WARNING Val Require

FAULT Laser Temp

FAULT Conditions

FAULT Det Sig High

FAULT Det Sig Lost

FAULT Outlier

FAULT Peak Center

Zero Calibrating…

Validation Status

Span Calibrating…
Offline Validating…
Online Validating…

Data Transferring…

Data Transfer Status

Transfer Success

Transfer Failure

Line 4 - Information

YOKOGAWA TDLS220

Analyzer Name

SN 76-1xxx-05-xx

Analyzer Serial No.

AO1: CONC xx-xx%/ppm/ppb

Configured 4-20mA output for

AO1, AO2, & AO3

AO2: TRANS xx-xx%

AO3: TEMP xx-xxF/C/K

10.0.0.35

Static IP Address

TEMP Act/Con/Fix xx F/C/K

Process Gas Temperature used for gas concentration

calculation

PRES Act/Con/Fix xx.x PsiA/

BarA

Process Gas Pressure used for gas concentration

calculation

OPL xx.x in/cm

Optical Path Length over which the analyzer is measuring

the target gas

Launch xx C

Launch unit internal temperature

Detect xx C

Detect unit internal temperature

This manual is related to the following products: