3 normal operating conditions, Normal operating conditions -4 – Yokogawa ADMAG CA User Manual
Page 80
![background image](/manuals/360061/80/background.png)
IM 1E8B0-01E
10-4
10. OUTLINE
When performing the Voltage Breakdown Test,
Insulation Resistance Test, or any unpowered
electeical test, wait 10 seconds after the power
supply is turned off before removing the housing
cover. Be sure to remove the Short Bar at
terminal “G”. After testing, return the Short Bar
to it’s correct position. Please be sure to use
resistance when discharging.
Screw tightening torque should be 12kgf.cm
(0.88ft-lb) or more, because the G-terminal is
thought as a protective grounding and should
conform to the Safety Requirements.
10.3 Normal Operating Conditions
• Ambient Temperature
: -20 to 50
°
C (-4 to 122˚F)
• Ambient Humidity
: 5 to 80%RH (no condensation)
• Power Supply
: Range 80 to 264 V AC / 100 to 130 V DC,
Range 20.4 to 28.8 V DC
• Power Supply Frequency for Power Supply: 47 to 63 Hz
• Fuse
: 2A, 250V (Time-Lag-Type)
• Measurable Fluid Conductivity : • Size 15 to 100mm (0.5 to 4 in): 0.01
µ
S/cm or
more
• Size 150, 200mm (6,8 in): 1
µ
S/cm or more
* In case of size 5 to 100mm (0.5 to 4 in) for
fluid of which conductivity is from 0.01
µ
S/
cm to 0.1
µ
S/cm, refer to accuracy in the
figure below.
Measured Data for Reference
; Measured Condition
Size
: 25mm(1 in.)
Fluid name
: Glycerin + Ethylene glycol
Viscosity
: 30cSt
Flow velocity
: 1m/s
Damping
: 3sec
Measured Time : 20sec
Short bar
CAUTION