6. FUNCTION AND DATA SETTINGS
6.3.5 Current Output During Alarm Occurrence
• The current output and display values during alarming can be selected in advance.
Display
Description
Set a value for current output to be used during alarms in parameter number "11"
Code
Contents
00
01
02
03
2.4mA or less
4.0mA
Hold
21.6mA or more
Default: 00
(2.4 mA or less)
6.3.6 Reversing Flow Direction
• The flow direction is set to “FORWARD” at the factory. This function enables to set
flow direction from “FORWARD” to “REVERSE”.
*
Note that measurements cannot be made both in reverse and forward directions.
Display
Description
Set the flow direction in parameter "14".
Code
Contents
00
01
Forward direction
Reverse direction to flow arrow
Default: 00
6.3.7 Limiting on Current Output
(1) 4 to 20 mA Low Cut Output (Current Output near by 0% Range)
• This function makes it possible to reduce noise in the 4mA region to reduce it
to 0%.
Display
Description
Setting range : 0 to 10%
0.5% 0.5%
4mA
5.6mA(10%)
Output
Set value
Input
Hysteresis: 1% fixed
Default: 0(%)